Spot-Type Photoelectric Pmoke Detector(JTY-GD-EI6012)
Product Overview:


1).“Two transmitters & one receptor” vertical bidirectional scattering technique, realizing a balanced response to different colors and smoke particles of different diameters in combination of the relative light intensity ratio algorithm, which is able to rule out interruptions caused by non-fire hazards to avoid false alarm.

2).Self-adaptive technology, which dynamically compensates environmental change and the aging of components, keeps the stability of the sensitivity of detector and extends its lifespan.









●Electronically addressed,unique ID,log on automatically,easy for installation and commissioning.
       ●Embedded base, slim design, fluid shape, not easy to absorb dust.
       ●Fire LED allows 360° viewing
       ●Rotating removable lid design,easy for cleaning the maze on site; whole buckled patent structure,
         easy for commissioning and maintenance.
       ●Water seepage prevention design.
       ●Patented technology for the maze realized balanced response to different color and particle smoke,
         can eliminate the interference caused by non-fire factors to avoid false alarm, azimuth response
         performance is superior.
      ●Adopts adaptive technology, it can do dynamic compensation for environmental change, aging of
        components, the detector sensitivity remains stable and prolong life.
      ●Self-test function, real-time detection of the internal circuitry to ensure long-term stable operation
        of the detector .




· Working temperature: -10℃ ~ +50 ℃

· Working humidity: ≤95% RH (No condensation of moisture)

· Working wire voltage: DC24V Pulsating voltage

· Wind speed: <5m/s

· Alarm indicating lamp: Red, flickers during routing inspection, keeps lighting during alarming· Protection level of casing: IP30

· Carried standard: GB 4715-2005 Spot-Type Smoke Detector

· Scattering: Bidirectional scattering

   · Standby current: <0.35mA

   · Alarming current: <0.8mA

   · Monitoring area: 60m2

   · Wiring system: Two-wire bus, non-polarized

   · Bus length: ≤2000m

   · Cleaning of detector: Rotatable, detachable

   · Color:EI White

       · PCB process: Waxdip





















Back